All Categories

Product Catalogue

Download Product Catalogue

100% Genuine Products

Supplier of industrial electrical products

1 year warranty

The products have a warranty

ATV12H075F1

5/5 - (5 votes)

variable speed drive, Altivar 12, 0.75kW, 1hp, 100 to 120V, 1 phase, with heat sink

Main documents

Main
Range of ProductAltivar 12
Product or Component TypeVariable speed drive
Product Specific ApplicationSimple machine
Mounting ModeCabinet mount
Communication Port ProtocolModbus
Supply frequency50/60 Hz +/- 5 %
[Us] rated supply voltage100…120 V – 15…10 %
Nominal output current4.2 A
Maximum Horse Power Rating1 hp
Motor power kW0.75 kW
Maximum Horse Power Rating1 hp
EMC filterWithout EMC filter
IP degree of protectionIP20
Complementary
Discrete input number4
Discrete output number2
Analogue input number1
Analogue output number1
Relay output number1
Physical interface2-wire RS 485
Connector Type1 RJ45
Continuous output current4.2 A 4 kHz
Method of accessServer Modbus serial
Speed drive output frequency0.5…400 Hz
Speed range1…20
Sampling duration20 ms +/- 1 ms logic input
10 ms analogue input
Linearity error+/- 0.3 % of maximum value analogue input
Frequency resolutionAnalog input converter A/D, 10 bits
Display unit 0.1 Hz
Time constant20 ms +/- 1 ms for reference change
Transmission Rate9.6 kbit/s
19.2 kbit/s
38.4 kbit/s
Transmission frameRTU
Number of addresses1…247
Data format8 bits, configurable odd, even or no parity
Communication serviceRead holding registers (03) 29 words
Write single register (06) 29 words
Write multiple registers (16) 27 words
Read/write multiple registers (23) 4/4 words
Read device identification (43)
Type of polarizationNo impedance
4 quadrant operation possibleFalse
Asynchronous motor control profileVoltage/frequency ratio (V/f)
Quadratic voltage/frequency ratio
Sensorless flux vector control
Maximum output frequency4 kHz
Transient overtorque150…170 % of nominal motor torque depending on drive rating and type of motor
Acceleration and deceleration rampsLinear from 0 to 999.9 s
S
U
Motor slip compensationPreset in factory
Adjustable
Switching frequency2…16 kHz adjustable
4…16 kHz with derating factor
Nominal switching frequency4 kHz
Braking to standstillBy DC injection
Brake chopper integratedFalse
Line current18.9 A 100 V heavy duty)
15.7 A 120 V heavy duty)
Maximum Input Current per Phase15.7 A
Maximum output voltage240 V
Apparent power1.9 kVA 240 V heavy duty)
Maximum transient current6.3 A 60 s heavy duty)
6.9 A 2 s heavy duty)
Network Frequency50-60 Hz
Relative symmetric network frequency tolerance5 %
Prospective line Isc1 kA
Base load current at high overload4.2 A
Power dissipation in WForced cooling 48.0 W
With safety function Safely Limited Speed (SLS)False
With safety function Safe brake management (SBC/SBT)False
With safety function Safe Operating Stop (SOS)False
With safety function Safe Position (SP)False
With safety function Safe programmable logicFalse
With safety function Safe Speed Monitor (SSM)False
With safety function Safe Stop 1 (SS1)False
With sft fct Safe Stop 2 (SS2)False
With safety function Safe torque off (STO)False
With safety function Safely Limited Position (SLP)False
With safety function Safe Direction (SDI)False
Protection typeLine supply overvoltage
Line supply undervoltage
Overcurrent between output phases and earth
Overheating protection
Short-circuit between motor phases
Against input phase loss in three-phase
Thermal motor protection via the drive by continuous calculation of I²t
Tightening torque10.62 lbf.in (1.2 N.m)
InsulationElectrical between power and control
Quantity per SetSet of 1
Width4.13 in (105 mm)
Height5.59 in (142 mm)
Depth6.15 in (156.2 mm)
Net Weight2.87 lb(US) (1.3 kg)
Environment
Operating altitude> 3280.84…6561.68 ft (> 1000…2000 m) with current derating 1 % per 100 m
<= 3280.84 ft (1000 m) without derating
Operating positionVertical +/- 10 degree
Product CertificationsNOM
CSA
C-tick
UL
GOST
RCM
KC
markingCE
StandardsUL 508C
UL 618000-5-1
EN/IEC 61800-5-1
EN/IEC 61800-3
Assembly styleWith heat sink
Electromagnetic compatibilityElectrical fast transient/burst immunity test level 4 EN/IEC 61000-4-4
Electrostatic discharge immunity test level 3 EN/IEC 61000-4-2
Immunity to conducted disturbances level 3 EN/IEC 61000-4-6
Radiated radio-frequency electromagnetic field immunity test level 3 EN/IEC 61000-4-3
Surge immunity test level 3 EN/IEC 61000-4-5
Voltage dips and interruptions immunity test EN/IEC 61000-4-11
Environmental class (during operation)Class 3C3 according to IEC 60721-3-3
Class 3S2 according to IEC 60721-3-3
Maximum acceleration under shock impact (during operation)150 m/s² at 11 ms
Maximum acceleration under vibrational stress (during operation)10 m/s² at 13…200 Hz
Maximum deflection under vibratory load (during operation)1.5 mm at 2…13 Hz
Volume of cooling air4226.83 Gal/hr(US) (16 m3/h)
Overvoltage categoryClass III
Regulation loopAdjustable PID regulator
Electromagnetic emissionRadiated emissions environment 1 category C2 EN/IEC 61800-3 2…16 kHz shielded motor cable
Conducted emissions with additional EMC filter environment 1 category C1 EN/IEC 61800-3 4…12 kHz shielded motor cable <16.40 ft (5 m)
Conducted emissions with additional EMC filter environment 1 category C2 EN/IEC 61800-3 4…12 kHz shielded motor cable <65.62 ft (20 m)
Conducted emissions with additional EMC filter environment 2 category C3 EN/IEC 61800-3 4…12 kHz shielded motor cable <65.62 ft (20 m)
Vibration resistance1 gn 13…200 Hz)EN/IEC 60068-2-6
1.5 mm peak to peak 3…13 Hz) – drive unmounted on symmetrical DIN rail – EN/IEC 60068-2-6
Shock resistance15 gn 11 ms EN/IEC 60068-2-27
Relative humidity5…95 % without condensation IEC 60068-2-3
5…95 % without dripping water IEC 60068-2-3
Noise level45 dB
Pollution degree2
Ambient air transport temperature-13…158 °F (-25…70 °C)
Ambient air temperature for operation14…122 °F (-10…50 °C) without derating
122…140 °F (50…60 °C) with current derating 2.2 % per °C
Ambient Air Temperature for Storage-13…158 °F (-25…70 °C)
Ordering and shipping details
CategoryUS1CP4B22042
Discount ScheduleCP4B
GTIN3606480071034
ReturnabilityYes
Country of originID
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height6.69 in (17.000 cm)
Package 1 Width7.68 in (19.500 cm)
Package 1 Length7.48 in (19.000 cm)
Package 1 Weight3.50 lb(US) (1.587 kg)
Unit Type of Package 2P06
Number of Units in Package 230
Package 2 Height29.53 in (75.000 cm)
Package 2 Width23.62 in (60.000 cm)
Package 2 Length31.50 in (80.000 cm)
Package 2 Weight131.40 lb(US) (59.600 kg)
Product Description

Schneider Driver

Frequently Asked Questions

A soft starter continuously controls the motor's voltage supply during the start-up phase. By adjusting the motor to the machine's load behavior, it ensures that mechanical operating equipment accelerates smoothly. This gradual acceleration lengthens the service life of the equipment, improves operating behavior, and smooths workflows, leading to more efficient and reliable operations.

A Schneider Electric drive, often referred to as a variable frequency drive (VFD) or variable speed drive (VSD), is an advanced device used to control the speed and torque of electric motors. These drives are integral components in modern industrial automation, providing precise motor control, energy efficiency, and enhanced operational performance.

✅ The primary difference between a Variable Frequency Drive (VFD) and a soft starter is their functionality. A VFD can vary the speed of a motor, providing precise control over its operation, while a soft starter only controls the starting and stopping phases of the motor. When considering an application, soft starters are typically more cost-effective and compact. However, if speed control is required, a VFD is the better choice.

✅ The primary difference between a Variable Frequency Drive (VFD) and a soft starter is their functionality. A VFD can vary the speed of a motor, providing precise control over its operation, while a soft starter only controls the starting and stopping phases of the motor. When considering an application, soft starters are typically more cost-effective and compact. However, if speed control is required, a VFD is the better choice.

Essentially, a Variable Frequency Drive (VFD) functions as a soft starter with added speed control capabilities. If your application requires speed variation, a VFD is the ideal choice. However, if you only need to control the inrush of current during startup and prefer a smaller, more cost-effective device, a soft starter is the better option.

Reviews

There are no reviews yet.

Be the first to review “ATV12H075F1”

Your email address will not be published. Required fields are marked *

Start typing to see products you are looking for.