Product Catalogue
Download Product Catalogue
100% Genuine Products
Supplier of industrial electrical products
1 year warranty
The products have a warranty
ATV12H075F1
variable speed drive, Altivar 12, 0.75kW, 1hp, 100 to 120V, 1 phase, with heat sink
- Stock status:
- In stock
- Manufacturer:
- Schneider
- Product code:
- ATV12H075F1
Main documents
Range of Product | Altivar 12 |
---|---|
Product or Component Type | Variable speed drive |
Product Specific Application | Simple machine |
Mounting Mode | Cabinet mount |
Communication Port Protocol | Modbus |
Supply frequency | 50/60 Hz +/- 5 % |
[Us] rated supply voltage | 100…120 V – 15…10 % |
Nominal output current | 4.2 A |
Maximum Horse Power Rating | 1 hp |
Motor power kW | 0.75 kW |
Maximum Horse Power Rating | 1 hp |
EMC filter | Without EMC filter |
IP degree of protection | IP20 |
Discrete input number | 4 |
---|---|
Discrete output number | 2 |
Analogue input number | 1 |
Analogue output number | 1 |
Relay output number | 1 |
Physical interface | 2-wire RS 485 |
Connector Type | 1 RJ45 |
Continuous output current | 4.2 A 4 kHz |
Method of access | Server Modbus serial |
Speed drive output frequency | 0.5…400 Hz |
Speed range | 1…20 |
Sampling duration | 20 ms +/- 1 ms logic input 10 ms analogue input |
Linearity error | +/- 0.3 % of maximum value analogue input |
Frequency resolution | Analog input converter A/D, 10 bits Display unit 0.1 Hz |
Time constant | 20 ms +/- 1 ms for reference change |
Transmission Rate | 9.6 kbit/s 19.2 kbit/s 38.4 kbit/s |
Transmission frame | RTU |
Number of addresses | 1…247 |
Data format | 8 bits, configurable odd, even or no parity |
Communication service | Read holding registers (03) 29 words Write single register (06) 29 words Write multiple registers (16) 27 words Read/write multiple registers (23) 4/4 words Read device identification (43) |
Type of polarization | No impedance |
4 quadrant operation possible | False |
Asynchronous motor control profile | Voltage/frequency ratio (V/f) Quadratic voltage/frequency ratio Sensorless flux vector control |
Maximum output frequency | 4 kHz |
Transient overtorque | 150…170 % of nominal motor torque depending on drive rating and type of motor |
Acceleration and deceleration ramps | Linear from 0 to 999.9 s S U |
Motor slip compensation | Preset in factory Adjustable |
Switching frequency | 2…16 kHz adjustable 4…16 kHz with derating factor |
Nominal switching frequency | 4 kHz |
Braking to standstill | By DC injection |
Brake chopper integrated | False |
Line current | 18.9 A 100 V heavy duty) 15.7 A 120 V heavy duty) |
Maximum Input Current per Phase | 15.7 A |
Maximum output voltage | 240 V |
Apparent power | 1.9 kVA 240 V heavy duty) |
Maximum transient current | 6.3 A 60 s heavy duty) 6.9 A 2 s heavy duty) |
Network Frequency | 50-60 Hz |
Relative symmetric network frequency tolerance | 5 % |
Prospective line Isc | 1 kA |
Base load current at high overload | 4.2 A |
Power dissipation in W | Forced cooling 48.0 W |
With safety function Safely Limited Speed (SLS) | False |
With safety function Safe brake management (SBC/SBT) | False |
With safety function Safe Operating Stop (SOS) | False |
With safety function Safe Position (SP) | False |
With safety function Safe programmable logic | False |
With safety function Safe Speed Monitor (SSM) | False |
With safety function Safe Stop 1 (SS1) | False |
With sft fct Safe Stop 2 (SS2) | False |
With safety function Safe torque off (STO) | False |
With safety function Safely Limited Position (SLP) | False |
With safety function Safe Direction (SDI) | False |
Protection type | Line supply overvoltage Line supply undervoltage Overcurrent between output phases and earth Overheating protection Short-circuit between motor phases Against input phase loss in three-phase Thermal motor protection via the drive by continuous calculation of I²t |
Tightening torque | 10.62 lbf.in (1.2 N.m) |
Insulation | Electrical between power and control |
Quantity per Set | Set of 1 |
Width | 4.13 in (105 mm) |
Height | 5.59 in (142 mm) |
Depth | 6.15 in (156.2 mm) |
Net Weight | 2.87 lb(US) (1.3 kg) |
Operating altitude | > 3280.84…6561.68 ft (> 1000…2000 m) with current derating 1 % per 100 m <= 3280.84 ft (1000 m) without derating |
---|---|
Operating position | Vertical +/- 10 degree |
Product Certifications | NOM CSA C-tick UL GOST RCM KC |
marking | CE |
Standards | UL 508C UL 618000-5-1 EN/IEC 61800-5-1 EN/IEC 61800-3 |
Assembly style | With heat sink |
Electromagnetic compatibility | Electrical fast transient/burst immunity test level 4 EN/IEC 61000-4-4 Electrostatic discharge immunity test level 3 EN/IEC 61000-4-2 Immunity to conducted disturbances level 3 EN/IEC 61000-4-6 Radiated radio-frequency electromagnetic field immunity test level 3 EN/IEC 61000-4-3 Surge immunity test level 3 EN/IEC 61000-4-5 Voltage dips and interruptions immunity test EN/IEC 61000-4-11 |
Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3 Class 3S2 according to IEC 60721-3-3 |
Maximum acceleration under shock impact (during operation) | 150 m/s² at 11 ms |
Maximum acceleration under vibrational stress (during operation) | 10 m/s² at 13…200 Hz |
Maximum deflection under vibratory load (during operation) | 1.5 mm at 2…13 Hz |
Volume of cooling air | 4226.83 Gal/hr(US) (16 m3/h) |
Overvoltage category | Class III |
Regulation loop | Adjustable PID regulator |
Electromagnetic emission | Radiated emissions environment 1 category C2 EN/IEC 61800-3 2…16 kHz shielded motor cable Conducted emissions with additional EMC filter environment 1 category C1 EN/IEC 61800-3 4…12 kHz shielded motor cable <16.40 ft (5 m) Conducted emissions with additional EMC filter environment 1 category C2 EN/IEC 61800-3 4…12 kHz shielded motor cable <65.62 ft (20 m) Conducted emissions with additional EMC filter environment 2 category C3 EN/IEC 61800-3 4…12 kHz shielded motor cable <65.62 ft (20 m) |
Vibration resistance | 1 gn 13…200 Hz)EN/IEC 60068-2-6 1.5 mm peak to peak 3…13 Hz) – drive unmounted on symmetrical DIN rail – EN/IEC 60068-2-6 |
Shock resistance | 15 gn 11 ms EN/IEC 60068-2-27 |
Relative humidity | 5…95 % without condensation IEC 60068-2-3 5…95 % without dripping water IEC 60068-2-3 |
Noise level | 45 dB |
Pollution degree | 2 |
Ambient air transport temperature | -13…158 °F (-25…70 °C) |
Ambient air temperature for operation | 14…122 °F (-10…50 °C) without derating 122…140 °F (50…60 °C) with current derating 2.2 % per °C |
Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) |
Category | US1CP4B22042 |
---|---|
Discount Schedule | CP4B |
GTIN | 3606480071034 |
Returnability | Yes |
Country of origin | ID |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 6.69 in (17.000 cm) |
Package 1 Width | 7.68 in (19.500 cm) |
Package 1 Length | 7.48 in (19.000 cm) |
Package 1 Weight | 3.50 lb(US) (1.587 kg) |
Unit Type of Package 2 | P06 |
Number of Units in Package 2 | 30 |
Package 2 Height | 29.53 in (75.000 cm) |
Package 2 Width | 23.62 in (60.000 cm) |
Package 2 Length | 31.50 in (80.000 cm) |
Package 2 Weight | 131.40 lb(US) (59.600 kg) |
Product Description
Schneider Electric
Schneider Electric is a multinational corporation specializing in energy management and automation solutions. With operations in over 100 countries, the company offers a wide range of products and services for various industries, including residential, commercial, and industrial.
Schneider Electric is focused on sustainability and innovation, aiming to help their customers manage energy efficiently and reduce their environmental impact.
Schneider Driver
Looking for reliable driver solutions for your Schneider Electric devices? Schneider Electric offers a range of drivers to ensure seamless integration and optimal performance of your automation and control systems. Whether you need drivers for industrial automation, energy management, or building automation, Schneider Electric provides robust and efficient drivers to meet your requirements.
Schneider Soft Starter
Schneider Electric offers a comprehensive range of soft starters designed to provide smooth and efficient motor starting and stopping. Soft starters are essential for reducing mechanical stress on motors and minimizing electrical surges, making them ideal for various industrial applications.
Altistart 12
The Schneider Electric Altistart 12 is a compact and efficient soft starter designed for the smooth control of 3-phase asynchronous motors. It is tailored to meet the needs of various simple and complex applications, ensuring reliable motor starting and stopping with reduced mechanical stress and enhanced operational efficiency.
Key Features of Altistart 12:
Motor Control:
- Provides smooth starting and stopping of motors, minimizing mechanical stress and extending the service life of equipment.
Compact Design:
- Space-saving design allows for easy integration into existing control panels and equipment.
Power Range:
- Supports a wide range of motor power ratings, making it suitable for various industrial applications.
Built-in Protections:
- Includes protections against overloads, short circuits, and phase imbalances, ensuring safe and reliable motor operation.
Ease of Use:
- Simple to install and configure, with user-friendly settings and interface.
ATV12H075F1
The Schneider Electric ATV12H075F1 is a variable speed drive from the Altivar 12 series, designed to provide precise control for commercial equipment and simple machines. This drive is engineered to enhance performance and efficiency in a variety of applications.
Key Features :
Power and Voltage:
- Rated power: 0.75kW (1hp)
- Input voltage: 100V to 120V AC, single-phase
Design:
- Equipped with a heatsink for efficient cooling in normal environments
- Fan-cooled enclosure for optimal thermal management
Advanced Functions:
- Features advanced PID control for precise process regulation
- Catch on the fly” function for seamless motor control
- Basic cabling and straightforward motor control settings
Configurations:
- Available with or without heatsink
- Options for an embedded EMC filter or standard version
Communication:
- Integrated Modbus communication protocol for easy integration and control
Compatibility and Standards:
- Conforms to IEC, UL, and other international standards
- Compatible with SoMove software for easy configuration and maintenance
The Schneider Electric ATV12H075F1 variable speed drive is a versatile and efficient solution designed to meet the needs of simple applications in industrial and commercial settings, ensuring reliable performance and significant energy savings.
Frequently Asked Questions
What is a Schneider Soft Starter?
✅ A soft starter is a solid-state device designed to protect AC electric motors from damage caused by sudden power surges. By limiting the large initial inrush of current during motor startup, soft starters ensure a smoother and safer operation, thereby extending the lifespan of the motor.
How Does a Soft Starter Work?
✅ A soft starter continuously controls the motor's voltage supply during the start-up phase. By adjusting the motor to the machine's load behavior, it ensures that mechanical operating equipment accelerates smoothly. This gradual acceleration lengthens the service life of the equipment, improves operating behavior, and smooths workflows, leading to more efficient and reliable operations.
what is a Schneider Drive
✅ A Schneider Electric drive, often referred to as a variable frequency drive (VFD) or variable speed drive (VSD), is an advanced device used to control the speed and torque of electric motors. These drives are integral components in modern industrial automation, providing precise motor control, energy efficiency, and enhanced operational performance.
What is the Difference Between VFD and Soft Starter?
✅ The primary difference between a Variable Frequency Drive (VFD) and a soft starter is their functionality. A VFD can vary the speed of a motor, providing precise control over its operation, while a soft starter only controls the starting and stopping phases of the motor. When considering an application, soft starters are typically more cost-effective and compact. However, if speed control is required, a VFD is the better choice.
Which is Better, VFD or Soft Starter?
✅ The primary difference between a Variable Frequency Drive (VFD) and a soft starter is their functionality. A VFD can vary the speed of a motor, providing precise control over its operation, while a soft starter only controls the starting and stopping phases of the motor. When considering an application, soft starters are typically more cost-effective and compact. However, if speed control is required, a VFD is the better choice.
Can a VFD Replace a Soft Starter?
✅Essentially, a Variable Frequency Drive (VFD) functions as a soft starter with added speed control capabilities. If your application requires speed variation, a VFD is the ideal choice. However, if you only need to control the inrush of current during startup and prefer a smaller, more cost-effective device, a soft starter is the better option.
Reviews
There are no reviews yet.