EZC100H3032
circuit breaker Easypact EZC100H – TMD – 32 A – 3 poles 3d
- Stock status:
- Call for availability
- Manufacturer:
- Schneider
- Product code:
- EZC100H3032
Main documents
İlgili ürünler
| Range of product | EasyPact |
|---|---|
| product or component type | Circuit breaker |
| Device short name | Easypact EZC100H |
| Circuit breaker name | Easypact EZC100H |
| Device application | Distribution |
| Poles description | 3P |
| Protected poles description | 3t |
| Network type | DC AC |
| Network frequency | 50/60 Hz |
| [In] rated current | 32 A at 40 °C |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2 |
| Breaking capacity code | H |
| Breaking capacity | 10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity | 5 kA at 125 V DC conforming to IEC 60947-2 5 kA at 250 V DC conforming to IEC 60947-2 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2 |
| Suitability for isolation | Yes conforming to IEC 60947-2 |
| Utilisation category | Category A |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit rating | 32 A at 50 °C |
| Protection type | Overload protection Short-circuit protection |
| Pollution degree | 3 conforming to IEC 60947 |
| Control type | Toggle |
|---|---|
| Mounting mode | Fixed |
| Mounting support | Backplate |
| Upside connection | Front |
| downside connection | Front |
| Mechanical durability | 8500 cycles |
| Electrical durability | Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2 |
| Connection pitch | 25 mm |
| Local signalling | Positive contact indication |
| Neutral protection setting | Without protection |
| earth-leakage protection | Without |
| Height | 130 mm |
| Width | 75 mm |
| Depth | 60 mm |
| Standards | EN/IEC 60947-1 JIS C8201-2-2 EN/IEC 60947-2 GB/T 14048.2 |
|---|---|
| IP degree of protection | IP20 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to EN 50102 |
| Ambient air temperature for operation | -25…70 °C |
| ambient air temperature for storage | -35…85 °C |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 9.5 cm |
| Package 1 Width | 8.5 cm |
| Package 1 Length | 14.0 cm |
| Package 1 Weight | 795.0 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 12 |
| Package 2 Height | 15.0 cm |
| Package 2 Width | 30.0 cm |
| Package 2 Length | 40.0 cm |
| Package 2 Weight | 9.852 kg |
| Unit Type of Package 3 | P12 |
| Number of Units in Package 3 | 192 |
| Package 3 Height | 50.0 cm |
| Package 3 Width | 80.0 cm |
| Package 3 Length | 120.0 cm |
| Package 3 Weight | 173.144 kg |
Product Description
EZC100H3032
The Schneider Electric EZC100H3032 is a 3-pole fixed circuit breaker from the EasyPact EZC100H range, designed for the protection of low-voltage electrical installations in industrial and building applications. It provides reliable thermal-magnetic protection at a competitive price, with fixed overload and instantaneous trip functions.

Key Features:
Rated Current: 32 A at 40 °C
Poles: 3P (protected poles 3t)
Network Type: AC/DC, 50/60 Hz
Rated Operational Voltage: 550 V AC / 250 V DC
Rated Insulation Voltage: 690 V AC
Breaking Capacity (Icu):
30 kA at 415 V AC
30 kA at 380–400 V AC
20 kA at 440 V AC
50 kA at 220–240 V AC
100 kA at 110–130 V AC
10 kA at 125–250 V DC (1–2 poles)

Rated Service Breaking Capacity (Ics): varies by voltage; up to 25 kA at 220–240 V AC
Trip Unit: Thermal-magnetic (TM-D)
Protection Types: Overload and short-circuit
Control: Toggle switch with positive contact indication
Mounting: Fixed on backplate, front-side connections
Mechanical Durability: 13,000 cycles
Dimensions (HxWxD): 130 x 75 x 60 mm
Connection Pitch: 25 mm
Standards Compliance: IEC/EN 60947-1 & 2, JIS C8201-2-2, GB/T 14048.2
IP/IK Protection: IP20 / IK07
Ambient Temperature: Operation -25…70 °C, Storage -35…85 °C
Applications:
Low-voltage distribution in buildings and industrial sites
Protection of circuits against overload and short-circuit conditions
Suitable for isolation as per IEC 60947-2 standards
Summary:
The EasyPact EZC100H3032 circuit breaker offers robust, reliable protection for low-voltage installations, with thermal-magnetic trip functionality, high breaking capacity, and compliance with international standards, making it ideal for industrial and commercial electrical systems.
Frequently Asked Questions
What does a switch disconnector do?
✅A switch disconnector, known as a disconnector switch or isolator switch, plays a crucial role in safely isolating power from electrical equipment during maintenance. This essential component not only ensures safety but also effectively breaks electrical circuits within large distribution systems.
What is the difference between a switch and a disconnector?
✅A switch serves as a vital control device, capable of supplying and interrupting the current flow required by consumers or control circuits throughout an appliance's lifespan. Meanwhile, a disconnector acts as a crucial safety feature, isolating the power supply to render the device inert for interlocking or maintenance purposes.
Can a switch disconnector trip?
✅A disconnector requires manual operation to cut power, ensuring circuit safety during maintenance but lacking overload protection. In contrast, a circuit breaker serves as a protective device, capable of thermally or magnetically tripping to safeguard circuits from overloads.
What is a switch disconnector fuse?
✅The switch disconnector is a widely used distribution equipment in factories, offering manual circuit switching, breaking, and power isolation capabilities. Additionally, the fuse switch disconnector provides effective short-circuit and overload protection for cables and power equipment within distribution systems.
Is a disconnect switch required?
✅Apart from adhering to IEC standards, compliance with the National Electric Code (NEC) requires the inclusion of a disconnect switch. According to this code, all large and permanently wired equipment must feature a disconnecting means within visible range.
What is the difference between switch disconnector and MCCB?
✅In simple terms, a switch toggles power on and off, while a circuit breaker interrupts the circuit during overload or faults. Switches control power, whereas breakers manage circuit interruptions. Recognizing these distinctions is vital for grasping their safety and utility.



















Değerlendirmeler