A9F73125

5/5 - (6 votes)

Miniature circuit breaker (MCB), Acti9 iC60N, 1P, 20A, B curve, 6000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)

Main documents

Main
Device application Distribution
Range Acti9
Product name Acti9 iC60
Product or component type Miniature circuit-breaker
Device short name IC60N
poles description 1P
Number of protected poles 1
[In] rated current 25 A
Network type DC
AC
Trip unit technology Thermal-magnetic
Curve code B
Breaking capacity 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
10 kA Icu at 60…72 V DC conforming to EN/IEC 60947-2
15 kA Icu at 12…60 V DC conforming to EN/IEC 60947-2
10 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
36 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
Utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2
Suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2
Standards EN 60898-1
IEC 60898-1
IEC 60947-2
EN 60947-2
Complementary
Network frequency 50/60 Hz
Magnetic tripping limit 4 x In +/- 20 %
[Ics] rated service breaking capacity 27 kA 75 % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 75 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
27 kA 75 % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 75 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
15 kA 75 % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz
15 kA 75 % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz
6000 A 100 % conforming to EN 60898-1 – 230 V AC 50/60 Hz
6000 A 100 % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
10 kA 100 % conforming to EN 60947-2 – 72 V DC
10 kA 100 % conforming to IEC 60947-2 – 72 V DC
15 kA 100 % conforming to EN 60947-2 – 12…60 V DC
15 kA 100 % conforming to IEC 60947-2 – 12…60 V DC
Limitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1
[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2
Contact position indicator Yes
Control type Toggle
local signalling Trip indicator
Mounting mode Fixed
Mounting support DIN rail
Comb busbar and distribution block compatibility Top or bottom: YES
9 mm pitches 2
Height 85 mm
Width 18 mm
Depth 78.5 mm
Net weight 0.215 kg
Colour White
Mechanical durability 20000 cycles
Electrical durability 10000 cycles
Connections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible
Wire stripping length 14 mm for top or bottom connection
Tightening torque 2 N.m top or bottom
Earth-leakage protection Without
Environment
IP degree of protection IP20 conforming to IEC 60529
IP20 conforming to EN 60529
Pollution degree 3 conforming to EN 60947-2
3 conforming to IEC 60947-2
Overvoltage category IV
Tropicalisation 2 conforming to IEC 60068-1
Relative humidity 95 % at 55 °C
Operating altitude 0…2000 m
Ambient air temperature for operation -35…70 °C
Ambient air temperature for storage -40…85 °C
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 7.5 cm
Package 1 Width 1.8 cm
Package 1 Length 9.5 cm
Package 1 Weight 115.0 g
Unit Type of Package 2 BB1
Number of Units in Package 2 12
Package 2 Height 8.0 cm
Package 2 Width 9.8 cm
Package 2 Length 22.5 cm
Package 2 Weight 1.45 kg
Unit Type of Package 3 S03
Number of Units in Package 3 132
Package 3 Height 30.0 cm
Package 3 Width 30.0 cm
Package 3 Length 40.0 cm
Package 3 Weight 16.428 kg
Product Description

Schneider Miniature Circuit Breaker

Frequently Asked Questions

When comparing Schneider and Siemens circuit breakers, both brands offer unique strengths and advantages, making them top choices in the industry.

Both Schneider and Siemens circuit breakers are excellent choices for protecting electrical systems. Schneider excels in versatility and precision engineering, while Siemens is known for its exceptional build quality and innovation. The choice between the two depends on specific needs and preferences, ensuring reliable protection and performance for any electrical system.

✅Miniature Circuit Breakers (MCBs) are essential for protecting electrical circuits from overcurrents and short circuits. There are three primary types of MCBs: Type B, Type C, and Type D. Each type is designed to respond to different levels of electrical surges in various settings.ft starters minimize the initial surge of power during startup by gradually increasing the voltage supply. This controlled power-up process prevents the motor from overheating, reducing the risk of temporary shutdowns and significantly extending the lifespan and durability of the motors.

Type B devices are engineered to trip when fault currents reach 3-5 times the rated current (In). For instance, a 10A Type B device will trip at 30-50A. Type C devices, on the other hand, are designed to trip at fault currents of 5-10 times In, which means a 10A device will trip at 50-100A. Lastly, Type D devices are intended to trip at fault currents of 10-20 times In, so a 10A device will trip at 100-200A.

✅ The product dimensions are (W) 54mm x (H) 85mm x (D) 77.5mm, and it weighs 0.31kg. It adheres to the IEC 60529 standard, offering a degree of protection rated at IP20 and IP40 when enclosed.

 

✅MCB Full Form - Miniature Circuit Breaker

✅Miniature Circuit Breaker

The full form of MCB is Miniature Circuit Breaker. An MCB is a type of electronic switch that operates automatically. It detects issues within a circuit by identifying excessive current flow, providing protection by interrupting the circuit to prevent damage.

✅ Miniature Circuit Breaker (MCB) - Definition, Types, and Uses

A Miniature Circuit Breaker (MCB) is a safety device equipped with an electro-mechanical mechanism that automatically interrupts the flow of excessive current in a circuit. Unlike fuses, MCBs can be reset and reused without manual replacement, enhancing safety and convenience in electrical systems.

Reviews

There are no reviews yet.

Be the first to review “A9F73125”

Your email address will not be published. Required fields are marked *

Start typing to see products you are looking for.