| Product Description | fixed-mounted circuit breaker 3-pole, size I, IEC In=630A to 690V, AC50/60Hz Icu=55kA at 500V rear connection horizontal Overcurrent release ETU 45 LSIN protection adjustable 0.4-1 in with cubicle bus Opt.: Comm. /measuring func./ground fault/ ZSS With manual operating mechanism with storage with mechanical request without 1st auxiliary release without 2nd auxiliary release 2NO+2NC |
| Product family | 3-pole |
| Product Lifecycle (PLM) | PM400:Phase Out Started |
| PLM Effective Date | Product phase-out since: 01.10.2023 |
| Notes | Successor hint: Successor portfolio 3WA; more information via www.siemens.com/3WA |
| Price data | |
| Price Group | 12M |
| List Price | Show prices |
| Customer Price | Show prices |
| Surcharge for Raw Material | see also metal factor (further details are available on the help page) |
| Metal Factor | LAO—– |
| Additional Product Information | ||
| EAN | Not available | |
| UPC | Not available | |
| Commodity Code | 85362090 | |
| LKZ_FDB/ CatalogID | LV10.1 | |
| Product Group | 3745 | |
| Group Code | P360 | |
| Country of origin | Czech Republic | |
| Compliance with the substance restrictions according to RoHS directive | Given | |
| Product class | C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit. | |
| WEEE (2012/19/EU) Take-Back Obligation | No | |
| REACH Art. 33 Duty to inform according to the current list of candidates | ||
| SCIP number | Not available | |
Product Description
3WL1106-2EB32-1AA2
The 3WL1106-2EB32-1AA2 is a fixed-mounted air circuit breaker designed to deliver reliable power protection in industrial and commercial settings. Part of Siemens’ trusted 3WL series, this 3-pole breaker features advanced protection mechanisms and optional communication and monitoring capabilities, ensuring efficient operation and enhanced safety.

Key Features and Specification
- Type: Fixed-mounted air circuit breaker.
- Poles: 3-pole configuration.
- Frame Size: Size I.
- Rated Current (In): 630A at up to 690V.
- Rated Voltage: Up to 690V AC, 50/60Hz.
- Breaking Capacity (Icu): 55kA at 500V.
- Overcurrent Release: ETU 45 LSIN with adjustable protection range **0.4 to 1 x In**.
Optional Features:
- Communication functions.
- Measuring functionality.
- Ground fault monitoring.
- Zero-sequence sensing (ZSS).
Operating Mechanism:
- Type: Manual operating mechanism with storage for reliable operation.
- Mechanical Request: Included for manual control and safety.
Additional Features:
- Connection: Rear horizontal connection with cubicle bus for streamlined installations.
Auxiliary Releases:
- 1st Auxiliary Release: Not included.
- 2nd Auxiliary Release: Not included.
- Auxiliary Contacts: 2NO+2NC configuration for operational monitoring and control.
Product Lifecycle:
- Lifecycle Status: PM400 – Phase-out started as of October 1, 2023.
- Replacement Recommendation: Siemens suggests transitioning to the 3WA series for modernized functionalities and extended product support.
Product Details:
- Product Family: 3-pole.
- Commodity Code: 85362090.
- Catalog ID: LV10.1.
- Product Group: 3745.
- Group Code: P360.
Applications:
Industrial and Commercial Installations:
- Designed for demanding applications requiring robust circuit protection and optional monitoring features.
Power Monitoring Systems:
- Equipped with communication and measurement options for seamless integration into modern power management setups.
Sensitive Environments:
- Ground fault and ZSS options enhance safety in critical installations.
Summary:
The Siemens 3WL1106-2EB32-1AA2 fixed-mounted circuit breaker provides dependable protection, advanced monitoring capabilities, and optional communication features. Designed with a 3-pole configuration and ETU 45 LSIN protection, it is suited for a wide range of applications. As the product enters the phase-out stage, Siemens recommends upgrading to the 3WA series for enhanced performance and future-ready features.
Frequently Asked Questions
What is the Range of Siemens Air Circuit Breakers (ACB)?
✅ Siemens Air Circuit Breakers (ACBs) are essential components for protection in low-voltage systems (LV) with advanced features for high breaking capacities. The Siemens ACB product lines, including the 3WL and 3WT series, are designed to meet a wide range of industrial needs.
Voltage Range: Siemens ACBs support systems with voltages up to 690V.
Current Rating: They are available with current ratings from 630 A up to 6300 A, accommodating various applications.
Key Features: Siemens ACBs offer exceptional performance with multiple breaking capacities and intelligent monitoring capabilities, making them reliable choices for demanding environments.
This flexibility in ratings and series options ensures Siemens ACBs are suitable for diverse low-voltage protection applications.
Which is Better: ACB or MCCB?
✅ Current Rating: ACBs are designed for higher current ratings than MCCBs, making them ideal for circuits with larger current demands.
✅ Adjustable Tripping: MCCBs offer adjustable tripping thresholds, which makes them versatile and suitable for a variety of circuit applications. This flexibility can give MCCBs an advantage in systems where different levels of protection are required.
In summary, ACBs are often preferred for high-current circuits, while MCCBs provide flexibility and adaptability in a range of applications. Each type has its strengths depending on the specific needs of the electrical system.
When Should You Use an ACB (Air Circuit Breaker)?
✅ Air Circuit Breakers (ACBs) are ideal for high-voltage applications, such as substations and power transmission systems, where they offer dependable protection by effectively interrupting heavy fault currents. Their robust design makes them a top choice for safeguarding critical electrical systems that require high fault-clearing capabilities.
What is the Purpose of a WL Circuit Breaker?
✅ The Siemens WL power circuit breaker is designed for low-voltage switchgear and switchboard applications, offering essential protection against short circuits and faults to prevent electrical damage or fire hazards. Commonly used as incoming-feeder, coupler, and outgoing-feeder circuit breakers, WL circuit breakers serve a wide range of applications in industrial, commercial, and infrastructure settings. They are a reliable choice for ensuring the safety and efficiency of electrical installations.
Are Siemens WL Circuit Breakers 100% Rated?
✅ Yes, Siemens WL circuit breakers are 100% rated, meaning they are designed for continuous operation at their full current rating without requiring external heat sinks. These breakers are engineered to meet the rigorous demands of standard industrial and commercial applications, ensuring reliable performance and protection for continuous, high-current usage.