circuit breaker 3VA1 IEC Frame 630 breaking capacity class S Icu=36 kA @ 415 V 4-pole, line protection TM240, ATAM, In=500 A overload protection Ir=350 A…500 A short-circuit protection Ii=5…10 x In N conductor unprotected nut keeper kit

Main documents

Product
Article Number (Market Facing Number)3VA1450-4EF42-0AA0
Product Description
Product family
3VA Molded Case Circuit Breakers up to 1600 A, IEC
Product Lifecycle (PLM)Active Product
Price data
Region Specific PriceGroup / Headquarter Price Group12P / 53J
List PriceShow prices
Customer PriceShow prices
Surcharge for Raw MaterialsNone
Metal FactorLOA—–
General technical data
insulation voltage / rated value800 V
operating voltage / at DC / rated value600 V
operating voltage / at AC / rated value690 V
power loss [W] / maximum122.7 W
power loss [W] / for rated value of the current / at AC / in hot operating state / per pole40.9 W
mechanical service life (operating cycles) / typical20 000
electrical endurance (operating cycles) / at AC-1 / at 380/415 V4 000
electrical endurance (operating cycles) / at AC-1 / at 690 V3 000
ground-fault monitoring versionWithout
WEEE (2012/19/EU) Take-Back ObligationYes
REACH Art. 33 Duty to inform according to the current list of candidatesnot available
Net Weight6.434 kg

Product Description

Performance & Features

  • 36 kA breaking capacity (Class S) ensures reliable protection for standard industrial distribution systems.

  • Thermal-magnetic TM240 release provides precise LI protection (overload & short-circuit).

  • 4-pole design with unprotected neutral suitable for systems where neutral monitoring is not required.

  • Adjustable protection settings allow proper coordination with downstream loads.

  • High endurance — up to 20,000 mechanical and 4,000 electrical operations at 415 V.

  • Rugged MCCB construction compatible with 3VA1 accessories.

  • Supplied with nut keeper kit for easy mounting.

  • Fully IEC-compliant for global installations.

Applications

  • Line and feeder protection in power distribution boards

  • Industrial and commercial electrical panels

  • Switching and protection of machinery and auxiliary systems

  • Installations requiring 4-pole breakers with unprotected neutral

  • Suitable for medium fault-level environments requiring 36 kA short-circuit capacity

Frequently Asked Questions

The full form of MCCB is Molded Case Circuit Breaker. A Siemens MCCB is designed to handle high electrical currents, often up to 1000A, making it highly reliable for industrial and commercial applications. These breakers provide advanced protection against overloads and short circuits, ensuring the safety of large electrical systems.

The main difference between an MCB (Miniature Circuit Breaker) and an MCCB (Molded Case Circuit Breaker) lies in their capacity and applications.

MCBs are generally used for low-power applications, with a short-circuit breaking capacity of up to 10–15 kA. They are best suited for residential and light commercial systems.

MCCBs, on the other hand, are designed for medium to high-power applications, with a breaking capacity ranging from 15 kA up to 100 kA and current ratings up to 1000A. This makes them ideal for industrial environments where large electrical loads need reliable protection.

✅ In 2025, the leading circuit breaker brands include Siemens, Schneider Electric, ABB, Eaton, and Legrand. Among them, Siemens MCCBs—especially the Sentron 3VA series—stand out for safety, durability, and advanced circuit protection in industrial and commercial applications.

Siemens QT, QP, QAF, and QPF breakers fit Siemens panels. However, not all breakers are interchangeable—e.g., a QT breaker cannot replace a QP breaker. Always check compatibility before replacing.

Reviews

There are no reviews yet.

Be the first to review “3VA1450-4EF42-0AA0”

Your email address will not be published. Required fields are marked *