All Categories

Product Catalogue

Download Product Catalogue

100% Genuine Products

Supplier of industrial electrical products

1 year warranty

The products have a warranty

METSEPM5660

5/5 - (4 votes)

power meter PowerLogic PM5660, 2 ethernet, up to 63th Harmonic, 1,1MB, RCM, 4DI/2DO 52 alarms

Main documents

Main
RangePowerLogic
Product namePowerLogic PM5000
Device short namePM5660
product or component typePower meter
Complementary
Power quality analysisUp to the 63rd harmonic
residual current monitoring
Metering typeMeasured neutral current
Calculated ground current
Residual current I0
Device applicationGateway
WAGES metering
Power monitoring
Multi-tariff
Type of measurementCurrent
Voltage
Frequency
Power factor
Energy
Active and reactive power
supply voltage100…300 V DC
90…528 V AC 45…65 Hz
Network frequency60 Hz
50 Hz
[In] rated current1 A
5 A
type of network3P + N
3P
1P + N
Maximum power consumption in VA16 VA at 480 V
Ride-through time35 ms 120 V AC typical
129 ms 230 V AC typical
50 ms 125 V DC typical
Display typeMonochrome graphic LCD
display resolution128 x 128 pixels
Sampling rate128 samples/cycle
Measurement current50…10000 mA
Analogue input typeVoltage (impedance 5 MOhm)
Current (impedance <= 0.3 mOhm)
Measurement voltage20…400 V AC 45…65 Hz between phase and neutral
20…828 V AC 45…65 Hz between phases
Frequency measurement range45…65 Hz
Number of inputs4 digital
Measurement accuracyApparent power +/- 0.5 %
Frequency +/- 0.05 %
Active energy +/- 0.2 %
Reactive energy +/- 1 %
Active power +/- 0.2 %
Voltage +/- 0.1 %
Power factor +/- 0.005
Current +/- 0.15 %
Reactive power +/- 1 %
Accuracy classClass 0.2S active energy conforming to IEC 62053-22
Number of outputs2 digital
Information displayedTariff (8)
Communication port protocolModbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none – 2 wires, insulation 2500 V
JBUS
Modbus TCP/IP at 10/100 Mbit/s, insulation 2500 V
Ethernet Modbus TCP/IP daisy chain
BACnet IP
DNP3 over ethernet
Communication port supportRS485
ETHERNET
Communication gatewayEthernet/serial
Data recordingEvent logs
Maintenance logs
Min/max of instantaneous values
Data logs
Alarm logs
Time stamping
Memory capacity1.1 MB
Web servicesAlarm notification by e-mail
Web server
Diagnostic via predefined web pages
Real time viewing of data
Ethernet serviceSNTP client
SNMP-Traps
Connections – terminalsVoltage circuit: screw terminal block4
Control circuit: screw terminal block2
Current transformer: screw terminal block6
RS485 link: screw terminal block4
Digital input: screw terminal block8
Digital output: screw terminal block4
Ethernet network: RJ45 connector2
mounting modeFlush-mounted
Mounting supportFramework
StandardsEN 50470-3
IEC 61557-12:2015
IEC 62053-22:2020
IEC 62053-24
IEC 60529
EN 50470-1
UL 61010-1
IEC 62053-23:2020
IEC 62052-11:2020
IEC 62052-31:2015
Product certificationsCE conforming to IEC 61010-1
CULus conforming to UL 61010-1
Width96 mm
Depth72 mm
Height96 mm
net weight450 g
Environment
Electromagnetic compatibilityLimits for harmonic current emissions class A conforming to IEC 61000-3-2
Conducted RF disturbances level 3 conforming to IEC 61000-4-6
Magnetic field at power frequency level 4 conforming to IEC 61000-4-8
Conducted and radiated emissions class B conforming to EN 55022
Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3
Electrostatic discharge – test level: 8 kV level 4 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
Surge immunity test level 4 conforming to IEC 61000-4-5
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
IP degree of protectionIP54 display: conforming to IEC 60529
IP30 rear: conforming to IEC 60529
Relative humidity5…95 % at 50 °C non-condensing
Pollution degree2
Ambient air temperature for operation-25…70 °C
ambient air temperature for storage-40…85 °C
Operating altitude<= 3000 m
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height11.5 cm
Package 1 Width12.5 cm
Package 1 Length12.5 cm
Package 1 Weight652.0 g
Unit Type of Package 2S03
Number of Units in Package 212
Package 2 Height30.0 cm
Package 2 Width30.0 cm
Package 2 Length40.0 cm
Package 2 Weight8.211 kg
Unit Type of Package 3P06
Number of Units in Package 396
Package 3 Height75.0 cm
Package 3 Width80.0 cm
Package 3 Length60.0 cm
Package 3 Weight73.688 kg
Product Description

Schneider Power Meters

Frequently Asked Questions

Push button switches can be classified as either normally open (NO) or normally closed (NC). Normally open (NO) switches, also known as "OFF" position switches, complete the circuit when actuated. In contrast, normally closed (NC) switches, or "ON" position switches, break the circuit when actuated. Understanding the difference between NO and NC push button switches is crucial for selecting the right type for your application, whether it's for industrial machinery, control panels, or electronic devices.

Push button switches come in two main types: single-pole and double-pole switches. The single-pole switch is the most common type, featuring a control device with a single input source and a single output source. This basic design makes single-pole switches ideal for a wide range of applications. Double-pole switches, on the other hand, have two input sources and two output sources, offering more complex control capabilities for advanced electrical systems.

No, a push button is not an analog sensor. An analog sensor provides a continuous output signal that varies in proportion to the measured quantity. In contrast, a push button provides a discrete output signal that changes state from one level to another when the button is pressed or released. This distinction makes push buttons ideal for applications requiring simple on/off control, unlike analog sensors that are used for more complex, variable measurements.

✅ A push button consists of several key components:

1. Button Actuator: This is the part you physically press. It is connected to an internal mechanism within the switch.

2. Contacts: Push button switches contain one or more sets of contacts, typically made from conductive materials like metal. In their default state, these contacts are separated.

When the button actuator is pressed, it moves the contacts together to complete an electrical circuit. This simple yet effective design is what makes push buttons reliable for various applications, from industrial machinery to everyday electronic devices.

A push button is a digital sensor. Unlike analog sensors, which provide a continuous range of values, digital sensors like push buttons have only two states: on or off. For example, when you press a push button, it changes from off to on, providing a discrete signal. Similarly, a digital light sensor can detect whether it is dark or bright, also giving a binary output. This clear distinction makes push buttons ideal for simple, straightforward control in various applications.

Reviews

There are no reviews yet.

Be the first to review “METSEPM5660”

Your email address will not be published. Required fields are marked *

Start typing to see products you are looking for.