All Categories

Product Catalogue

Download Product Catalogue

100% Genuine Products

Supplier of industrial electrical products

1 year warranty

The products have a warranty

31341

5/5 - (1 vote)

switch disconnector, Compact INS2500, 2500A, standard version with black rotary handle, 4 poles

Main documents

Main
RangeComPact
Product nameComPacT INS
Product or component typeSwitch disconnector
Poles description4P
Network typeAC
DC
Network frequency50/60 Hz
[Ie] rated operational currentAC-21B: 2500 A AC 50/60 Hz 220/240 V
AC-21B: 2500 A AC 50/60 Hz 380/415 V
AC-21B: 2500 A AC 50/60 Hz 440/480 V
AC-21B: 2500 A AC 50/60 Hz 480 V NEMA
AC-21B: 2500 A AC 50/60 Hz 500/525 V
AC-21B: 2500 A AC 50/60 Hz 660/690 V
AC-22B: 2500 A AC 50/60 Hz 220/240 V
AC-22B: 2500 A AC 50/60 Hz 380/415 V
AC-22B: 2500 A AC 50/60 Hz 440/480 V
AC-22B: 2500 A AC 50/60 Hz 480 V NEMA
AC-22B: 2500 A AC 50/60 Hz 500/525 V
AC-22B: 2500 A AC 50/60 Hz 660/690 V
DC-21B: 2500 A DC 125 V 2 poles in series
DC-22B: 2500 A DC 125 V 2 poles in series
DC-21B: 2500 A DC 250 V 4 poles in series
DC-22B: 2500 A DC 250 V 4 poles in series
[Ui] rated insulation voltage1000 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage12 kV
[Ith] conventional free air thermal current2500 A at 60 °C
[Icm] rated short-circuit making capacity105 kA switch-disconnector alone 690 V AC at 50/60 Hz
105 kA with upstream protection circuit breaker 690 V AC at 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
250 V DC
Suitability for isolationYes
Contact position indicatorYes
Visible breakNo
Pollution degree3
Complementary
Control typeDirect front rotary handle
handle colourBlack
Mounting modeFixed
mounting supportRail
Plate
Upside connectionFront
downside connectionFront
Rated dutyUninterrupted
Intermittent duty classClass 120 – 60 %
[Icw] rated short-time withstand current50 kA during 0.5 s conforming to IEC 60947-3
11 kA during 30 s conforming to IEC 60947-3
13 kA during 20 s conforming to IEC 60947-3
30 kA during 3 s conforming to IEC 60947-3
50 kA during 0.8 s conforming to IEC 60947-3
50 kA during 1 s conforming to IEC 60947-3
Mechanical durability3000 cycles
Electrical durabilityAC-21B: 100 cycles 220/240 V AC 50/60 Hz
AC-21B: 100 cycles 380/415 V AC 50/60 Hz
AC-21B: 100 cycles 440/480 V AC 50/60 Hz
AC-21B: 100 cycles 480 V AC 50/60 Hz conforming to NEMA
AC-21B: 100 cycles 500/525 V AC 50/60 Hz
AC-21B: 100 cycles 660/690 V AC 50/60 Hz
AC-22B: 100 cycles 220/240 V AC 50/60 Hz
AC-22B: 100 cycles 380/415 V AC 50/60 Hz
AC-22B: 100 cycles 440/480 V AC 50/60 Hz
AC-22B: 100 cycles 480 V AC 50/60 Hz conforming to NEMA
AC-22B: 100 cycles 500/525 V AC 50/60 Hz
AC-22B: 100 cycles 660/690 V AC 50/60 Hz
DC-21B: 100 cycles 125 V DC 2 poles in series
DC-22B: 100 cycles 125 V DC 2 poles in series
DC-21B: 100 cycles 250 V DC 4 poles in series
DC-22B: 100 cycles 250 V DC 4 poles in series
Connection pitch70 mm
height440 mm
Width462.5 mm
Depth227.5 mm
Net weight45 kg
Environment
StandardsIEC 60947-1
IEC 60947-3
product certificationsKEMA-KEUR
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height34.500 cm
Package 1 Width61.400 cm
Package 1 Length59.700 cm
Package 1 Weight62.200 kg
Product Description

Schneider Electric offers a wide range of switch disconnectors designed to ensure safety, reliability, and efficiency in electrical installations. These switch disconnectors serve as essential components in industrial and commercial settings, allowing for the safe isolation of electrical circuits during maintenance or emergencies.

31341 - schneider switch disconnector

Schneider switch disconnectors are engineered with robust construction, advanced features, and compliance with international standards to meet the diverse needs of various applications. With options available for different voltage levels, current ratings, and environmental conditions, Schneider switch disconnectors provide flexible solutions for power distribution and control systems.
Whether it’s for motor control, distribution boards, or switchgear assemblies, Schneider’s switch disconnectors deliver high performance and peace of mind in electrical operations.

31341

The Schneider product with code 31341 is a Compact INS2500 switch disconnector, featuring a 4-pole non-automatic design with a black rotary handle. It is compliant with IEC 60947-1 and IEC60947-3 standards, suitable for isolation with positive contact indication.

31341 - schneider 31341
With an operational current of 4000A at 415VAC in categories AC21A, AC22A, and AC23A, and a rated voltage of 690VAC 50/60Hz or 250VDC, it offers easy operation and high performance in interrupting current. Additionally, it is a Class II insulation level front-face device according to IEC 60664 standard.

Frequently Asked Questions

A switch serves as a vital control device, capable of supplying and interrupting the current flow required by consumers or control circuits throughout an appliance's lifespan. Meanwhile, a disconnector acts as a crucial safety feature, isolating the power supply to render the device inert for interlocking or maintenance purposes.

A disconnector requires manual operation to cut power, ensuring circuit safety during maintenance but lacking overload protection. In contrast, a circuit breaker serves as a protective device, capable of thermally or magnetically tripping to safeguard circuits from overloads.

The switch disconnector is a widely used distribution equipment in factories, offering manual circuit switching, breaking, and power isolation capabilities. Additionally, the fuse switch disconnector provides effective short-circuit and overload protection for cables and power equipment within distribution systems.

Apart from adhering to IEC standards, compliance with the National Electric Code (NEC) requires the inclusion of a disconnect switch. According to this code, all large and permanently wired equipment must feature a disconnecting means within visible range.

In simple terms, a switch toggles power on and off, while a circuit breaker interrupts the circuit during overload or faults. Switches control power, whereas breakers manage circuit interruptions. Recognizing these distinctions is vital for grasping their safety and utility.

Değerlendirmeler

Henüz değerlendirme yapılmadı.

“31341” için yorum yapan ilk kişi siz olun

E-posta adresiniz yayınlanmayacak. Gerekli alanlar * ile işaretlenmişlerdir

Start typing to see products you are looking for.