31131

5/5 - (3 votes)

switch disconnector, Compact INS400, 400A, with red rotary handle and yellow front, 4 poles

Main documents

Main
RangeComPact
product or component typeSwitch disconnector
Product nameComPacT INS
Poles description4P
Network typeAC
DC
Network frequency50/60 Hz
[Ie] rated operational currentAC-22A: 400 A AC 50/60 Hz 220/240 V
AC-22A: 400 A AC 50/60 Hz 380/415 V
AC-22A: 400 A AC 50/60 Hz 440/480 V
AC-22A: 400 A AC 50/60 Hz 480 V NEMA
AC-22A: 400 A AC 50/60 Hz 500/525 V
AC-22A: 400 A AC 50/60 Hz 660/690 V
AC-23A: 400 A AC 50/60 Hz 220/240 V
AC-23A: 400 A AC 50/60 Hz 380/415 V
AC-23A: 400 A AC 50/60 Hz 440/480 V
AC-23A: 400 A AC 50/60 Hz 480 V NEMA
AC-23A: 400 A AC 50/60 Hz 500/525 V
AC-23A: 400 A AC 50/60 Hz 660/690 V
DC-22A: 400 A DC 125 V 2 poles in series
DC-22A: 400 A DC 250 V 4 poles in series
DC-23A: 400 A DC 125 V 2 poles in series
DC-23A: 400 A DC 250 V 4 poles in series
[Ui] rated insulation voltage750 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
8 kV conforming to IEC 60947-3
[Ith] conventional free air thermal current400 A at 60 °C
[Icm] rated short-circuit making capacity330 kA with upstream protection circuit breaker 690 V AC at 50/60 Hz
50 kA switch-disconnector alone 690 V AC at 50/60 Hz
[Ue] rated operational voltage250 V DC
690 V AC 50/60 Hz
Suitability for isolationYes
Contact position indicatorYes
Visible breakNo
Pollution degree3
Complementary
Control typeRed and yellow rotary handle
handle colourRed
Mounting modeFixed
Mounting supportPlate
Rail
Upside connectionFront
downside connectionFront
Maximum powerAC-23: 110 kW at 220/240 V AC 50/60 Hz
AC-23: 110 kW at 230 V AC 50/60 Hz (NEMA)
AC-23: 200 kW at 380/415 V AC 50/60 Hz
AC-23: 220 kW at 440 V AC 50/60 Hz
AC-23: 220 kW at 480 V AC 50/60 Hz (NEMA)
AC-23: 250 kW at 500/525 V AC 50/60 Hz
AC-23: 400 kW at 660/690 V AC 50/60 Hz
Rated dutyUninterrupted
[Icw] rated short-time withstand current11.5 kA during 3 s conforming to IEC 60947-3
20 kA during 1 s conforming to IEC 60947-3
4 kA during 30 s conforming to IEC 60947-3
4.9 kA during 20 s conforming to IEC 60947-3
Mechanical durability10000 cycles
Electrical durabilityAC-22A: 1500 cycles 440 V AC 50/60 Hz
AC-22A: 1500 cycles 500 V AC 50/60 Hz
AC-22A: 1500 cycles 690 V AC 50/60 Hz
AC-23A: 1500 cycles 440 V AC 50/60 Hz
AC-23A: 1500 cycles 500 V AC 50/60 Hz
AC-23A: 1500 cycles 690 V AC 50/60 Hz
DC-23A: 1000 cycles 250 V DC 4 poles in series
Connection pitch45 mm
Height205 mm
Width185 mm
Depth130 mm
net weight4.9 kg
Environment
StandardsIEC 60947-1
IEC 60947-3
Product certificationsCCC
KEMA-KEUR
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Ambient air temperature for operation-25…70 °C
ambient air temperature for storage-50…85 °C
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height19.5 cm
Package 1 Width18.8 cm
Package 1 Length22.5 cm
Package 1 Weight5.498 kg
Unit Type of Package 2S04
Number of Units in Package 24
Package 2 Height30.0 cm
Package 2 Width40.0 cm
Package 2 Length60.0 cm
Package 2 Weight22.758 kg
Product Description

Schneider Switch Disconnector

Frequently Asked Questions

A switch serves as a vital control device, capable of supplying and interrupting the current flow required by consumers or control circuits throughout an appliance's lifespan. Meanwhile, a disconnector acts as a crucial safety feature, isolating the power supply to render the device inert for interlocking or maintenance purposes.

A disconnector requires manual operation to cut power, ensuring circuit safety during maintenance but lacking overload protection. In contrast, a circuit breaker serves as a protective device, capable of thermally or magnetically tripping to safeguard circuits from overloads.

The switch disconnector is a widely used distribution equipment in factories, offering manual circuit switching, breaking, and power isolation capabilities. Additionally, the fuse switch disconnector provides effective short-circuit and overload protection for cables and power equipment within distribution systems.

Apart from adhering to IEC standards, compliance with the National Electric Code (NEC) requires the inclusion of a disconnect switch. According to this code, all large and permanently wired equipment must feature a disconnecting means within visible range.

In simple terms, a switch toggles power on and off, while a circuit breaker interrupts the circuit during overload or faults. Switches control power, whereas breakers manage circuit interruptions. Recognizing these distinctions is vital for grasping their safety and utility.

Değerlendirmeler

Henüz değerlendirme yapılmadı.

“31131” için yorum yapan ilk kişi siz olun

E-posta adresiniz yayınlanmayacak. Gerekli alanlar * ile işaretlenmişlerdir

Start typing to see products you are looking for.