All Categories

Product Catalogue

Download Product Catalogue

100% Genuine Products

Supplier of industrial electrical products

1 year warranty

The products have a warranty

IMDIFL12H

5/5 - (3 votes)

VIGILOHM 12 CHANNEL FAULT LOCATOR WITH MODBUS HOSPITAL – 110-230VAC – 125/250VDC

Main documents

Main
RangeVigilohm
Device short nameIFL12H
product or component typeInsulation fault locator
Device applicationHospital
Earthing systemIT
User languageFrench
German
Italian
Portuguese
Russian
Spanish
English
Chinese
Complementary
Network rated voltage0…230 V – DC
0…230 V – AC at 45…65 Hz
Number of channels12
Type of measurementNetwork insulation resistance – measurement range: 200 Ohm…250 kOhm
Local signallingYellow indicator light: insulation fault
Yellow flashing indicator light: communication
Green/red indicator light: product status
Green indicator light: satisfactory insulation
Yellow flashing indicator light: transient fault
Threshold settingAlarm: 50…200 kOhm
alarm per channelAlarm threshold: settable per feeder
Accuracy+/- 15 %
Response time<= 5 s
auxiliary supply voltage125…250 V DC +/- 15 %
110…230 V AC 50/60 Hz +/- 15 %
Power consumption in VA25 VA
power consumption in W10 W
Test functionRemote test
Manual
Auto test at start and every 5h
output contact1 C/O standard or fail-safe
breaking capacity250 V – AC at 6 A
48 V – DC at 1 A
Communication port protocolModbus
Communication port supportRS485
Display typeDigital display
Mounting modeFlush-mounted
Clip-on
Mounting supportDIN rail
Panel
Mounting positionHorizontal
Vertical
Connections – terminalsPower supply: removable screw terminal block0.2…2.5 mm²
Output relay: removable screw terminal block0.2…2.5 mm²
Toroids inputs: removable screw terminal block0.2…1.5 mm²
Communication: removable screw terminal block0.2…2.5 mm²
Voltage inputs: removable screw terminal block0.2…2.5 mm²
MaterialThermoplastic
Overvoltage categoryIII
net weight0.5 kg
Cut-out dimensions92 x 104 mm
Height110 mm
Width108 mm
Depth59 mm
Environment
IP degree of protectionCase: IP20
Front face: IP54
Environmental characteristicExposure to damp heat not in service conforming to IEC 60068-2-30
Exposure to damp heat in service conforming to IEC 60068-2-56
Salt mist conforming to IEC 60068-2-52
Operating altitude<= 3000 m
Pollution degree2
Relative humidity5…92 %
Type of installationIndoor
StandardsIEC 61010-1
IEC 60364-7-710
IEC 61326-2-4
IEC 61557-9
Product certificationsDNV-GL
EAC
CE
UL
cULus
Ambient air temperature for operation-25…55 °C
ambient air temperature for storage-40…85 °C
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height9.7 cm
Package 1 Width18.2 cm
Package 1 Length13.5 cm
Package 1 Weight550.0 g
Unit Type of Package 2S03
Number of Units in Package 28
Package 2 Height30.0 cm
Package 2 Width30.0 cm
Package 2 Length40.0 cm
Package 2 Weight5.14 kg
Product Description

Schneider Power Monitoring and Control

Frequently Asked Questions

✅Power monitoring systems typically comprise a power metering device to gauge overall facility power consumption and assess power quality. Coupled with a monitoring system, these tools track energy distribution within the facility post-metering.

A Power Monitoring Device plays a crucial role in measuring power consumption, facilitating energy-saving endeavors. While electricity itself remains invisible, it represents a convenient and ubiquitous form of energy that transforms into various manifestations such as heat, light, sound, and power, all of which are extensively utilized.

Enhance safety and boost process availability with Vigilohm's range of insulation monitoring devices (IMDs). Designed for IT (ungrounded) networks, these devices offer a straightforward, dependable solution for insulation monitoring, communication, and fault location. Discover how this streamlined offering can elevate both personnel and equipment safety while optimizing process availability.

Insulation Monitors by DOLD: Insulation Monitoring Made Simple

DOLD's insulation monitors provide seamless insulation monitoring solutions. In the event of an insulation fault, the measuring circuit triggers, allowing a proportional small current to flow. The device's electronics evaluate this current, issuing a notification if the insulation resistance drops below a predefined threshold (response value).

Explore the Importance of Isolation Monitoring in High-Voltage Vehicle Systems

Isolation monitoring stands as a pivotal safety feature in high-voltage vehicle systems. In modern vehicles, the high-voltage system remains completely isolated from the vehicle chassis. This design safeguards against electrical shock by preventing a single fault in the high-voltage system from posing a risk to individuals.

Reviews

There are no reviews yet.

Be the first to review “IMDIFL12H”

Your email address will not be published. Required fields are marked *

Start typing to see products you are looking for.