All Categories

Product Catalogue

Download Product Catalogue

100% Genuine Products

Supplier of industrial electrical products

1 year warranty

The products have a warranty

IMDIFL12H

5/5 - (3 votes)

VIGILOHM 12 CHANNEL FAULT LOCATOR WITH MODBUS HOSPITAL – 110-230VAC – 125/250VDC

Main documents

Main
Range Vigilohm
Device short name IFL12H
product or component type Insulation fault locator
Device application Hospital
Earthing system IT
User language French
German
Italian
Portuguese
Russian
Spanish
English
Chinese
Complementary
Network rated voltage 0…230 V – DC
0…230 V – AC at 45…65 Hz
Number of channels 12
Type of measurement Network insulation resistance – measurement range: 200 Ohm…250 kOhm
Local signalling Yellow indicator light: insulation fault
Yellow flashing indicator light: communication
Green/red indicator light: product status
Green indicator light: satisfactory insulation
Yellow flashing indicator light: transient fault
Threshold setting Alarm: 50…200 kOhm
alarm per channel Alarm threshold: settable per feeder
Accuracy +/- 15 %
Response time <= 5 s
auxiliary supply voltage 125…250 V DC +/- 15 %
110…230 V AC 50/60 Hz +/- 15 %
Power consumption in VA 25 VA
power consumption in W 10 W
Test function Remote test
Manual
Auto test at start and every 5h
output contact 1 C/O standard or fail-safe
breaking capacity 250 V – AC at 6 A
48 V – DC at 1 A
Communication port protocol Modbus
Communication port support RS485
Display type Digital display
Mounting mode Flush-mounted
Clip-on
Mounting support DIN rail
Panel
Mounting position Horizontal
Vertical
Connections – terminals Power supply: removable screw terminal block0.2…2.5 mm²
Output relay: removable screw terminal block0.2…2.5 mm²
Toroids inputs: removable screw terminal block0.2…1.5 mm²
Communication: removable screw terminal block0.2…2.5 mm²
Voltage inputs: removable screw terminal block0.2…2.5 mm²
Material Thermoplastic
Overvoltage category III
net weight 0.5 kg
Cut-out dimensions 92 x 104 mm
Height 110 mm
Width 108 mm
Depth 59 mm
Environment
IP degree of protection Case: IP20
Front face: IP54
Environmental characteristic Exposure to damp heat not in service conforming to IEC 60068-2-30
Exposure to damp heat in service conforming to IEC 60068-2-56
Salt mist conforming to IEC 60068-2-52
Operating altitude <= 3000 m
Pollution degree 2
Relative humidity 5…92 %
Type of installation Indoor
Standards IEC 61010-1
IEC 60364-7-710
IEC 61326-2-4
IEC 61557-9
Product certifications DNV-GL
EAC
CE
UL
cULus
Ambient air temperature for operation -25…55 °C
ambient air temperature for storage -40…85 °C
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 9.7 cm
Package 1 Width 18.2 cm
Package 1 Length 13.5 cm
Package 1 Weight 550.0 g
Unit Type of Package 2 S03
Number of Units in Package 2 8
Package 2 Height 30.0 cm
Package 2 Width 30.0 cm
Package 2 Length 40.0 cm
Package 2 Weight 5.14 kg
Product Description

Schneider Power Monitoring and Control

Frequently Asked Questions

✅Power monitoring systems typically comprise a power metering device to gauge overall facility power consumption and assess power quality. Coupled with a monitoring system, these tools track energy distribution within the facility post-metering.

A Power Monitoring Device plays a crucial role in measuring power consumption, facilitating energy-saving endeavors. While electricity itself remains invisible, it represents a convenient and ubiquitous form of energy that transforms into various manifestations such as heat, light, sound, and power, all of which are extensively utilized.

Enhance safety and boost process availability with Vigilohm's range of insulation monitoring devices (IMDs). Designed for IT (ungrounded) networks, these devices offer a straightforward, dependable solution for insulation monitoring, communication, and fault location. Discover how this streamlined offering can elevate both personnel and equipment safety while optimizing process availability.

Insulation Monitors by DOLD: Insulation Monitoring Made Simple

DOLD's insulation monitors provide seamless insulation monitoring solutions. In the event of an insulation fault, the measuring circuit triggers, allowing a proportional small current to flow. The device's electronics evaluate this current, issuing a notification if the insulation resistance drops below a predefined threshold (response value).

Explore the Importance of Isolation Monitoring in High-Voltage Vehicle Systems

Isolation monitoring stands as a pivotal safety feature in high-voltage vehicle systems. In modern vehicles, the high-voltage system remains completely isolated from the vehicle chassis. This design safeguards against electrical shock by preventing a single fault in the high-voltage system from posing a risk to individuals.