✅Schneider VIGILOHM | 415 VCA⚡【 ️IMD-IM20 】
All Categories

Product Catalogue

Download Product Catalogue

100% Genuine Products

Supplier of industrial electrical products

1 year warranty

The products have a warranty

Main
Range Vigilohm
Device short name IM20
product or component type Insulation monitoring device
Device application Marine application
Standard environment application
electrical circuit type Medium or low disturbed network
Earthing system IT
User language Spanish
English
French
German
Russian
Chinese
Portuguese
Italian
Complementary
Network rated voltage 0…600 V – AC at 45…440 Hz (device connected to neutral)
0…480 V – AC at 45…440 Hz (device connected to phase)
0…345 V – DC
Data recording Alarm logs
Type of measurement Network insulation resistance – measurement range: 0.1 kOhm…10 MOhm
Earth leakage capacitance – measurement range: 0.1…40 µF
History of alarms
Local signalling Green indicator light: satisfactory insulation resistance
White indicator light: below prevention threshold
Orange indicator light: below fault threshold
Orange flashing indicator light: transient fault
Threshold setting Prevent: 1 kOhm…1 MOhm
Fault: 0.5…500 kOhm
Time delay range 0…5 min for signalling circuit
Response time <= 5 s
auxiliary supply voltage 110…415 V AC 45…440 Hz +/- 15 %
125…250 V DC +/- 15 %
Power consumption in VA 12 VA
Measurement voltage 75 V
Measurement current 0…0.4 mA
internal impedance 110 kOhm – AC at 0.1…440 Hz
Test function Manual
Self test
output contact 1 C/O standard or fail-safe
breaking capacity 250 V – AC at 6 A
12…24 V – DC at 6 A
Input function Injection inhibition: 24 V DC 5 mA
Communication port protocol Modbus
Communication port support RS485
Display type Digital display
Mounting mode Clip-on
Flush-mounted
Mounting support DIN rail
Panel
Connections – terminals Removable screw terminal block0.2…2.5 mm²
Material Thermoplastic
Overvoltage category III
net weight 0.25 kg
Height 110 mm
Width 96 mm
Depth 59 mm
Environment
Dielectric strength 4000 V – AC
5500 V – DC
IP degree of protection Front face: IP52
Environmental characteristic Exposure to damp heat not in service conforming to IEC 60068-2-30
Exposure to damp heat in service conforming to IEC 60068-2-56
Salt mist conforming to IEC 60068-2-52
Operating altitude <= 3000 m
Pollution degree 2
Type of installation Indoor
Standards IEC 60364-4-41
IEC 61010-1
IEC 61557-8
IEC 61326-2-4
Product certifications BV
DNV
CE
EAC
RMRS
Ambient air temperature for operation -25…55 °C
ambient air temperature for storage -40…70 °C
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 10.5 cm
Package 1 Width 13.5 cm
Package 1 Length 16.5 cm
Package 1 Weight 443.0 g
Unit Type of Package 2 S03
Number of Units in Package 2 8
Package 2 Height 30.0 cm
Package 2 Width 30.0 cm
Package 2 Length 40.0 cm
Package 2 Weight 4.17 kg
Product Description

Schneider Power Monitoring and Control

Frequently Asked Questions

✅Power monitoring systems typically comprise a power metering device to gauge overall facility power consumption and assess power quality. Coupled with a monitoring system, these tools track energy distribution within the facility post-metering.

A Power Monitoring Device plays a crucial role in measuring power consumption, facilitating energy-saving endeavors. While electricity itself remains invisible, it represents a convenient and ubiquitous form of energy that transforms into various manifestations such as heat, light, sound, and power, all of which are extensively utilized.

Enhance safety and boost process availability with Vigilohm's range of insulation monitoring devices (IMDs). Designed for IT (ungrounded) networks, these devices offer a straightforward, dependable solution for insulation monitoring, communication, and fault location. Discover how this streamlined offering can elevate both personnel and equipment safety while optimizing process availability.

Insulation Monitors by DOLD: Insulation Monitoring Made Simple

DOLD's insulation monitors provide seamless insulation monitoring solutions. In the event of an insulation fault, the measuring circuit triggers, allowing a proportional small current to flow. The device's electronics evaluate this current, issuing a notification if the insulation resistance drops below a predefined threshold (response value).

Explore the Importance of Isolation Monitoring in High-Voltage Vehicle Systems

Isolation monitoring stands as a pivotal safety feature in high-voltage vehicle systems. In modern vehicles, the high-voltage system remains completely isolated from the vehicle chassis. This design safeguards against electrical shock by preventing a single fault in the high-voltage system from posing a risk to individuals.

Reviews

There are no reviews yet.

Be the first to review “IMD-IM20”

Your email address will not be published. Required fields are marked *

Start typing to see products you are looking for.