Main
Range Compact
Product type or equipment Isolator switch
Product Name ComPacT INS
Description of the poles 3P
Network type AC
DC
Network frequency 50/60Hz
[Ie] rated operational current AC-22A: 630 A AC 50/60 Hz 220/240 V
AC-22A: 630 A AC 50/60 Hz 380/415 V
AC-22A: 630 A AC 50/60 Hz 440/480 V
AC-22A: 630 A AC 50/60 Hz 480 V NEMA
AC-22A: 630 A AC 50/60 Hz 500/525 V
AC-22A: 630 A AC 50/60 Hz 660/690 V
AC-23A: 630 A AC 50/60 Hz 220/240 V
AC-23A: 630 A AC 50/60 Hz 380/415 V
AC-23A: 630 A AC 50/60 Hz 440/480 V
AC-23A: 630 A AC 50/60 Hz 480 V NEMA
AC- 23A: 630 A AC 50/60 Hz 500/525 V
AC-23A: 630 A AC 50/60 Hz 660/690 V
DC-22A: 550 A DC 125 V 2 poles in series
DC-23A: 550 A DC 125 V 2 poles in series
DC-23B: 630 A DC 125 V 2 poles in series
[Ui] rated insulation voltage 750 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV
8 kV conforming to IEC 60947-3
[Ith] conventional thermal current 630 A at 60°C
[Icm] rated short-circuit closing power 330 kA with upstream protective circuit breaker 690 V AC at 50/60 Hz
50 kA disconnector only 690 V AC at 50/60 Hz
[Ue] rated operational voltage 125 V DC
690 V AC 50/60 Hz
Sectioning ability Yes
Fully visible cut Yes
Visible break No
Degree of pollution 3
Complementary
Order type Direct front rotating handle
Handle color Black
Installation mode Fixed
Mounting bracket
Platinum Rail
Upstream connection Facade
Downstream connection Facade
Maximum power AC-23: 200 kW at 220/240 V AC 50/60 Hz
AC-23: 200 kW at 230 V AC 50/60 Hz (NEMA)
AC-23: 315 kW at 380/415 V AC 50/60 Hz
AC -23: 375 kW at 480 V AC 50/60 Hz (NEMA)
AC-23: 400 kW at 440 V AC 50/60 Hz
AC-23: 400 kW at 500/525 V AC 50/60 Hz
AC-23: 560 kW at 660/690 V AC 50/60 Hz
Assigned service Uninterrupted
[Icw] rated short-term admissible current 11.5 kA for 3 s conforming to IEC 60947-3
20 kA for 1s conforming to IEC 60947-3
4 kA for 30 s conforming to IEC 60947-3
4.9 kA for 20 s conforming to IEC 60947- 3
Mechanical life 10000 cycles
Electrical life AC-22A: 1500 cycle 440 V AC 50/60 Hz
AC-22A: 1500 cycle 500 V AC 50/60 Hz
AC-22A: 1500 cycle 690 V AC 50/60 Hz
AC-23A: 1500 cycle 440 V AC 50/ 60 Hz
AC-23A: 1500 cycle 500 V AC 50/60 Hz
AC-23A: 1500 cycle 690 V AC 50/60 Hz
DC-23A: 1000 cycle 125 V DC 2 poles in series
DC-23B: 200 cycle 125 V DC 2 poles in series
“No” connection 45mm
Height 205mm
Width 185mm
Depth 130mm
Product weight 4.6kg
Environment
Standards IEC 60947-3
IEC 60947-1
Product certifications CCC
KEMA-KEUR
Degree of IP protection IP40 conforming to IEC 60529
IK shock resistance IK07 conforming to EN 50102
Ambient operating temperature -25…70°C
Ambient storage temperature -50…85°C
Packaging
Packaging type 1 PCE
Number of products in packaging 1 1
Package Height 1 19.2cm
Package width 1 19.2cm
Package length 1 22.4 cm
Package weight 1 4.988 kg
Packaging type 2 S04
Number of products in packaging 2 4
Package Height 2 30cm
Package width 2 40cm
Package length 2 60cm
Package weight 2 20,718 kg
Packaging type 3 P12
Number of products in packaging 3 16
Package height 3 50cm
Package width 3 80cm
Package length 3 120cm
Package weight 3 91.984 kg
Product Description

Schneider Switch Disconnector

Frequently Asked Questions

A switch serves as a vital control device, capable of supplying and interrupting the current flow required by consumers or control circuits throughout an appliance's lifespan. Meanwhile, a disconnector acts as a crucial safety feature, isolating the power supply to render the device inert for interlocking or maintenance purposes.

A disconnector requires manual operation to cut power, ensuring circuit safety during maintenance but lacking overload protection. In contrast, a circuit breaker serves as a protective device, capable of thermally or magnetically tripping to safeguard circuits from overloads.

The switch disconnector is a widely used distribution equipment in factories, offering manual circuit switching, breaking, and power isolation capabilities. Additionally, the fuse switch disconnector provides effective short-circuit and overload protection for cables and power equipment within distribution systems.

Apart from adhering to IEC standards, compliance with the National Electric Code (NEC) requires the inclusion of a disconnect switch. According to this code, all large and permanently wired equipment must feature a disconnecting means within visible range.

In simple terms, a switch toggles power on and off, while a circuit breaker interrupts the circuit during overload or faults. Switches control power, whereas breakers manage circuit interruptions. Recognizing these distinctions is vital for grasping their safety and utility.